UPS de baixa frequência online 20KVA~200KVA(208V)

REF: UPI-TU Series Categoria: Etiquetas: , ,

ModelUPI-TU20/30UPI-TU40/60UPI-TU80UPI-TU100/120UPI-TU160/200
Capacidade nominal20/30KVA40/60KVA80KVA100/120KVA160/200KVA
Size(L*W*Hmm)540x620x1120mm660x865x1550mm645x1070x1320mm705x1135x1418mm1600x1182x1962mm
N.W.(kg)225/273437/500660710/7901540/2030
Installation MethodTower
Input
Input Voltage Range120/208V or 127/220Vac +-20%
AC Input Frequency Range50Hz/60Hz+-10%
WiresThree phase+N+G
Saída
Output Voltage120/208V or 127/220Vac +-1%
Output Frequency(Battery Mode)50Hz/60Hz+-0.1%
Output Wave(Battery Mode)Pure Sine Wave
THD<2% liner load/<5% non-linear load
Crest factor3:1
Fator de potência0.9
Overload recoveryAutomático
Voltage regulationLoad balance+-1%
Capacidade de sobrecarga 125% for 12 mins,150% for 1 min
WiresThree phase+N+E
Bateria
Tipo de BateriaVRLA or lithiom ion battery
Full load autonomy3-15 mins or extend
Typical recharge time4 hours,90%
Battery managementAutotest,adjustable battery transfer point and alarm setting
Battery protectionBreaker protection,turn the system off when the battery is low,battery
Hardware protectionsBreaker for input,output,battery and bypass.Fast acting fuses in DC,fans,redundant power suppliers,temperature sensors,on-off switch and audible alarms.
BypassStatic solid state,automatic and manual operation without interruption for mantenance.
Emergency switchLocal EPO and/or Remote
Transfer Time0ms
MostrarTela sensível ao toque LCD
AlarmAudible and visual alarms for abnormal conditions
ComunicaçãoRS232,SNMP-RJ45, GPRS(optional)
Ambiente
Temperatura de operação0℃~40℃
Storage temperature-15℃~60℃
Barulho<60dB
Altitude1000m(above derating)
EficiênciaPower saving mode>98%,AC-AC>91%,Inverter>92%