| DC input | |
| Max.DC voltage(Vdc) | 1500 |
| DC voltage range(Vdc) | 800~1500 | 900~1500 | 1000~1500 |
| DC max. current(A) | 3206 | 3742 | 3872 |
| Auto-buffering function | Yes |
| Grid-tied AC output | |
| Rated AC output power(KW) | 2500 | 3000 | 3450 |
| Max.AC output power(KVA) | 2750 | 3300 | 3795 |
| Rated grid-tied voltage(Vdc) | 550 | 600 | 690 |
| Grid voltage range | -15%~10% (settable) |
| Rated grid frequency(Hz) | 50/60 |
| Max.output current(A) | 2886 | 3176 | 3176 |
| Power factor | >0.99 (at rated power) |
| Adjustable power factor | 1 leading ~ 1 lagging |
| THDi | <3% (at rated power) |
| Off-grid AC output | |
| Rated AC output voltage(Vdc) | 550 | 600 | 690 |
| Output voltage precision | 1% |
| Max.output current(A) | 2886 | 3176 | 3176 |
| THDu | <3% (liner load) |
| Rated output frequency(Hz) | 50/60 |
| Overloading capability | 110% overload |
| Transformer | | | |
| Isolation mode | Oil-immersed transformer |
| Transformer rated power | 2500KVA | 3000KVA | 3450KVA |
| LV/MV voltage | 0.55/10~35KV optional | 0.6/10~35KV optional | 0.69/10~35KV optional |
| Transformer vector | Dy11 |
| PCS efficiency | |
| Max. efficiency | 99.00% |
| General data | |
| Operation temperature | – 35℃~ 60℃ (>45℃ derating) |
| Relative humidity | 0 ~100%(non-condensing) |
| IP raito | IP55 |
| Altitude(m) | 4,000m (>3,000 Derating) |
| Cooling | Intelligent forced air cooling |
| Dimension(WxHxD)mm | 6058*2896*2438 |
| Display | LCD touch screen |
| Communication protocol | Modbus-RTU,Modbus-TCP,IEC61850,IEC104 |
| Communication interface | RS485,Ethernet |