Utilities-scale Power Conversion System & Transformer Turnkey System Skids EU

1500Vdc Power Conversion System & Transformer Turnkey System Skids

Highly integrated

  • Efficient layout to improve space utilization
  • Full turnkey system delivery with standardized physical and digital connections.
  • Automative peak shaving operation.
  • Integrated design of “converter” and “step-up” to realize the integrated delivery of products

Efficient and stable

  • Advanced ANPC three-level topology, max. converter efficiency 99.00%
  • Adapt to high temperature, salt, and extreme cold etc. environment
  • Long-term overload, 45ºC full load operation

Lean intelligence

  • Integrated high-efficiency liquid cooling system,longer lifespan.
  • Multi-branch DC design prevents battery looping currents.
  • With LVRT and HVRT.
  • VSG/PQ/VF mode capabilities.
  • Islanding,balck start capabilities.
  • 4-quadrant active and reactive power control.
  • Fast power response(<10ms).

Flexible configuration

  • Integrated PCS and booster,highly compact.
  • Modular design for the 1500V system.
  • Standardized design, easy to expand and maintain.
  • Fast deployment and quick setup on-site.
  • Reduces your carbon footprint.
  • Wide DC voltage range for 1500V system
  • Various applications such as peak shaving, frequency modulation, auxiliary grid connection for new energy system, etc.

Model NumberPCST1-2150KEUPCST1-2580KEUPCST1-3010KEUPCST1-3450KEU
LV equipment
Rated power(KVA)2150258030103450
DC voltage range(Vdc)1000~1500
Full load voltage range(Vdc)1070~1500
DC max. current(A)2*10402*12482*14562*1664
Number of DC branches2*1/52*1/62*1/72*1/4/8
LC & auxiliary equipment
Aux.transformer100KVA/690V/400V
UPSUp to 1KVA(0.5h standard)
Output 400V/50Hz Three phase four wire (3P4W)
MV equipment
Rated AC output power(KVA)2150258030103450
Rated grid frequency(Hz)50/60
Power factor>0.99 (at rated power)
Adjustable power factor1 leading ~ 1 lagging
THDi<3% (at rated power)
Overloading capability100% overload
Transformer
Isolation modeOil-immersed transformer
LV/MV voltage0.69/10~33KV optional0.69/10~33KV optional0.69/10~33KV optional0.69/10~33KV optional
Transformer vectorDy11
Cooling typeKNAN
General data
Operation temperature– 30℃~ 55℃ (>45℃ derating)
Relative humidity0 ~95%(non-condensing)
IP raitoIP54,C4
Altitude(m)1,000m
Cooling Air cooling
Dimension(WxHxD)mm7600*2553*2200
Weight(Kg)<20T
Communication protocolModbus-RTU,Modbus-TCP,IEC61850,IEC104