1500Vdc Power Conversion System & Transformer Turnkey System Skids
Highly integrated
- Efficient layout to improve space utilization
- Full turnkey system delivery with standardized physical and digital connections.
- Automative peak shaving operation.
- Integrated design of “converter” and “step-up” to realize the integrated delivery of products
Efficient and stable
- Advanced ANPC three-level topology, max. converter efficiency 99.00%
- Adapt to high temperature, salt, and extreme cold etc. environment
- Long-term overload, 45ºC full load operation
Lean intelligence
- Integrated high-efficiency liquid cooling system,longer lifespan.
- Multi-branch DC design prevents battery looping currents.
- With LVRT and HVRT.
- VSG/PQ/VF mode capabilities.
- Islanding,balck start capabilities.
- 4-quadrant active and reactive power control.
- Fast power response(<10ms).
Flexible configuration
- Integrated PCS and booster,highly compact.
- Modular design for the 1500V system.
- Standardized design, easy to expand and maintain.
- Fast deployment and quick setup on-site.
- Reduces your carbon footprint.
- Wide DC voltage range for 1500V system
- Various applications such as peak shaving, frequency modulation, auxiliary grid connection for new energy system, etc.
| Model Number | PCST1-2150KEU | PCST1-2580KEU | PCST1-3010KEU | PCST1-3450KEU |
|---|---|---|---|---|
| LV equipment | ||||
| Rated power(KVA) | 2150 | 2580 | 3010 | 3450 |
| DC voltage range(Vdc) | 1000~1500 | |||
| Full load voltage range(Vdc) | 1070~1500 | |||
| DC max. current(A) | 2*1040 | 2*1248 | 2*1456 | 2*1664 |
| Number of DC branches | 2*1/5 | 2*1/6 | 2*1/7 | 2*1/4/8 |
| LC & auxiliary equipment | ||||
| Aux.transformer | 100KVA/690V/400V | |||
| UPS | Up to 1KVA(0.5h standard) | |||
| Output | 400V/50Hz Three phase four wire (3P4W) | |||
| MV equipment | ||||
| Rated AC output power(KVA) | 2150 | 2580 | 3010 | 3450 |
| Rated grid frequency(Hz) | 50/60 | |||
| Power factor | >0.99 (at rated power) | |||
| Adjustable power factor | 1 leading ~ 1 lagging | |||
| THDi | <3% (at rated power) | |||
| Overloading capability | 100% overload | |||
| Transformer | ||||
| Isolation mode | Oil-immersed transformer | |||
| LV/MV voltage | 0.69/10~33KV optional | 0.69/10~33KV optional | 0.69/10~33KV optional | 0.69/10~33KV optional |
| Transformer vector | Dy11 | |||
| Cooling type | KNAN | |||
| General data | ||||
| Operation temperature | – 30℃~ 55℃ (>45℃ derating) | |||
| Relative humidity | 0 ~95%(non-condensing) | |||
| IP raito | IP54,C4 | |||
| Altitude(m) | 1,000m | |||
| Cooling | Air cooling | |||
| Dimension(WxHxD)mm | 7600*2553*2200 | |||
| Weight(Kg) | <20T | |||
| Communication protocol | Modbus-RTU,Modbus-TCP,IEC61850,IEC104 | |||
| Communication interface | RS485,Ethernet,CAN | |||