| DC input | |
| No.of DC inputs | 12 | 16 |
| Max.DC voltage(Vdc) | 1500 |
| DC voltage range(Vdc) | 1000~1500 |
| DC max. current(A) | 2694(224.5A*12) | 3592(224.5A*16) |
| Grid-tied AC output | |
| Rated AC output power(KW) | 2640(220KVA*12@35℃ ) | 3520(220KVA*16@35℃ ) |
| Max.AC output current(A) | 2209.2(184.1A*12) | 2945.6(184.1A*16) |
| AC voltage range(Vdc) | 607~759V (adjustable) |
| Rated grid frequency(Hz) | 50/60 |
| Power factor | -1 ~+1 |
| THDi | <1.5% (100% load) |
| Off-grid AC output | |
| Rated AC output voltage(Vdc) | 690,3W+PE |
| AC voltage range(Vdc) | 607~759V (adjustable) |
| AC voltage distortion | <1.5% (100% linear load) |
| DC voltage component | <0.5% UN(liner balance load) |
| Rated output frequency(Hz) | 50/60 |
| Unbalanced load capability | 100% |
| Transformer | | |
| Isolation mode | Oil-immersed transformer |
| Transformer rated power | 2640KVA @35℃ | 3520KVA @35℃ |
| LV/MV voltage | 0.69/10~35KV optional |
| Transformer vector | Dy11 |
| Transformer cooling type | ONAN (KNAN optional) |
| Oil type | Mineral oil(PCB free) or degradable oil on request |
| General data | |
| Max. efficiency | 99.00% |
| Europe efficiency | 98.50% |
| Operation temperature | – 40℃~ +60℃ (>45℃ derating) |
| Relative humidity | 0 ~100%(non-condensing) |
| IP raito | IP55 |
| Altitude(m) | 4,000m (>2,000 Derating) |
| Cooling | Intelligent forced air cooling |
| Dimension(WxHxD)mm | 6058*2896*2438 |
| Display | LCD touch screen |
| Communication protocol | Modbus-RTU,Modbus-TCP,IEC61850,IEC104 |
| Communication interface | RS485/CAN/Ethernet |